updatedAt: 2025-09-29T20:15:27.000Z
agentTools:
  projectIndex: https://modelling.modoenergy.com/llms.txt
---

# Demand

How we model ERCOT demand.

# ERCOT Demand

## Nodal Demand

### Description

We model demand at the substation (node) level with hourly resolution to capture both intraday shape and seasonal effects. The primary input is ERCOT’s Long-Term Load Forecast (LTLF), which provides weather-zone hourly profiles through 2045 and separates demand into:

* **Base** (economic) load
* **Behind-the-meter (BTM) rooftop PV**
* **Electric vehicles (EVs)**
* **Large flexible loads (LFLs)**
* **Large loads from Contracts & Officer Letters** (hydrogen, data centers, crypto, oil & gas, industrial)

We use LTLF for **Base, BTM PV, EV, and LFL**. We **do not** take ERCOT’s Contracts & Officer Letters into our demand assumptions; instead, we apply Modo’s **in-house bottom-up large-load build**, informed by our research team. **Oil & gas electrification** assumptions are anchored to ERCOT’s **Permian Basin Reliability Planning Study**.

### Central Case

<Image border={false} src="https://files.readme.io/c9d4ce20e8d387351b95342f79be6e3807cf2ec639fc36e6c1aa751ad60c13f0-image.png" />

<br />

### Load profiles

Each load component exhibits a different profile based on function, price responsiveness and any on-site behind-the-meter generation.

<Image align="center" border={false} caption="Representative large load profiles" src="https://files.readme.io/cd2c927382d13073fe52a143c8a2f6206d19d4fc2a6c8877eb68b19b407b87d5-image.png" />

<br />

### Load Sensitivity

ERCOT’s LTLF timeseries data represents a **“median” (p50) weather year** using 2008 data. We extend this by enabling **alternative weather-year load shapes** to be layered on top of ERCOT’s values—supporting **higher/lower demand cases** and aligning the demand shapes with our **renewable load-factor weather years** for consistent scenario analysis.

<Image border={false} src="https://files.readme.io/b488144d1c9b972fb29d97271cad445eadf52a49f769c1651ddc709e583cbf03-image.png" />

<br />

### Assumptions and Caveats

* Beyond 2034, demand growth is applied at the weather zone level, without explicit nodal detail.

### Data Sources

| Source                                             | Description                                                                 | Link                                                                                                                                                      |
| :------------------------------------------------- | :-------------------------------------------------------------------------- | :-------------------------------------------------------------------------------------------------------------------------------------------------------- |
| \*\*ERCOT Long-Term Load Forecast                  | Provides weather zone hourly projections until 2045                         | [ERCOT LTLF](https://www.ercot.com/gridinfo/load/forecast)                                                                                                |
| **ERCOT Regional Transmission Plan (RTP)**         | Provides zonal to nodal distribution factors                                | [ERCOT RTP](https://www.ercot.com/gridinfo/transmission/)                                                                                                 |
| **ERCOT Permian Basin Reliability Planning Study** | Supports modeling of additional oil & gas-related load growth in West Texas | [Permian Basin Study](https://www.ercot.com/files/docs/2024/06/28/Permian%20Basin%20Reliability%20Plan%20Study%20-%20Workshop%20-%20June%2028%202024.pdf) |
| **Organization press releases**                    | Used to identify additional large, non-O\&G loads coming online.            |                                                                                                                                                           |